Harmonic analysis pqm data in 150kv grid of tso tennet in brabant, the Netherlands

This paper aims to provide an insight into the measured background changes of harmonics due to operational changes in a typical Dutch transmission grid. Multiple use cases on different locations throughout a meshed 150kV grid have been considered. The nodes that were studied had measured exceedances of planning levels or were indicated to be critical for the future in earlier studies. This study provides an insight into the measured response of harmonics with respect to different operational changes such as specific scheduled outages that occurred and the impact of capacitor banks. Per use-cas... Mehr ...

Verfasser: Broekman, W.L.
van Waes, J.B.M.
Ćuk, V.
Cobben, J.F.G.
Dokumenttyp: Artikel
Erscheinungsdatum: 2021
Reihe/Periodikum: Broekman , W L , van Waes , J B M , Ćuk , V & Cobben , J F G 2021 , ' Harmonic analysis pqm data in 150kv grid of tso tennet in brabant, the Netherlands ' , Renewable Energy & Power Quality Journal , vol. 19 , 280 , pp. 298-303 . https://doi.org/10.24084/repqj19.280
Schlagwörter: -Background harmonics / High-voltage / Power quality / /dk/atira/pure/sustainabledevelopmentgoals/affordable_and_clean_energy / name=SDG 7 - Affordable and Clean Energy
Sprache: Englisch
Permalink: https://search.fid-benelux.de/Record/base-29195896
Datenquelle: BASE; Originalkatalog
Powered By: BASE
Link(s) : https://research.tue.nl/en/publications/a41225b0-3343-45fe-b939-29b4abae7ee1